Description
Low Transmission Switchgear
Description :
(EC/NEMA Standard LT Panel using 1250A ACB (Adjustable) and Others Accessories as
per IEC requirements for LT Panel of Electric Sub-Station Supply of 16
SWG Sheet steel clad, dust and vermin proof,
free standing,
floor mounting type
Complete Factory assembled 3- phase
4-wire 415V,
50 Hz indoor type Low Tension Switchgear panel.
having Suitable Earthing 1250A hard drawn
electrolytic copper bus bar & comprising of followings.
Panel Size: ( L 700 x W 550 x H 1700)mm Min.
Incoming :
01 No.1250A, 65kA, ACB with Shunt Opening &
Closing Release,
Under Voltage Trip Coil,
Gear Motor,
Door Frame,
Ultimate breaking capacity V AC 50/60 HzIcu
(kA rms) at 440 V:42/50/66/130:
Rated service breaking capacity Ics (kA rms) at
440 V:42/50/130
Rated short-time withstand current V AC 50/60
Hz Icw (kA rms) 0.5 s:42/50/10,
Position of neutral: Left/right Compliant with
IEC /EN 60947-2 Annex H or Equivalent.
03 Nos. Current Transformer, ratio : 800/5A
With Suitable accuracy and burden.
01 Nos. Multi meter, 0 ? 9999A
03 Nos. Indicating Lamp.
01 Set of Control Fuse.
01 Nos Panel Type Digital/Analog Ampare Meter,
Volt Meter,
01 Nos. every device OVERCURRENT &
EARTH FAULT RELAYS,
Under-Over Voltage Relay,
Phase Sequence Relay
Accessories :
Connecting Wire: 1 set.
Power Cord.
2mm or 4mm safety Jack: 1 set.
User Manual: 1 Set
Others :
Product Origin: China, Taiwan, Japan
Manufacturing: Assemble in Bangladesh
Installation
Training
Warranty: 01 year